Basic TMS-5041 Partial Discharge Monitor

Simple, continuous partial discharge monitoring system with manual data storage.

Sensor Compatibility:

  • HFT Series Partial Discharge Sensor
  • HFTC Series Partial Discharge Sensor
  • PDC Series Partial Discharge Sensor

Description

The  Basic TMS-5041 is a four channel partial discharge trending system with a true color LCD to display all the necessary information for the commissioning and surveillance of  Medium and High Voltage Equipment. The noise gating channel and variable LP Filter separates noise from actual partial discharge signals. The actual partial discharge levels for each individual channel (phase) are displayed on a  bar graph and real time partial discharge activities are displayed in oscilloscope view and through a colorised phase resolved pattern.

The touch functionality of the LCD display allows the user to set alarms and parameters, and to store and visualise the partial discharge signals without the use of an additional computer. Eight optional 4-20mA input channels are included to record machine operation conditions such as MW, MVA and temperatures,  in addition to the partial discharge signals. The optional Modbus RTU interface allows an easy integration into the exisiting SCADA/DCS system. Individual 4-20mA and relay outputs per channel are available.

This makes the Basic TMS-5041 a cost effective partial discharge monitoring system for permanent installation with manual data recording.

 

Key Features

  • Online.
  • Continuous acquisition and monitoring.
  • Manual data acquisition and storage.
  • High Resolution PRPD Pattern
  • Built in full colour 4.3″ touch display screen.
  • Noise Elimination trough Gating Channel and variable Frequency Range.
  • Intelligent analysis and diagnostics.
  • Integrated with SCADA and 3rd party monitoring systems.
  • Designed for complete commissioning without additional hardware
  • 4 Analouge outputs, 8 inputs for operation parameter recording.
  • IEC – 60270 compliant.
  • Wall mount version available

 

Technical Data

  • PD Input Channels (Multiplexed + Gating): 4+1
  • Selectable LP Filter: 40KHz to 5MHz
  • Selectable HP Filter: 800kHz to 300MHz
  • Signal Gain (HW): 40dB
  • Acquisition Time Intervall: 1 to 600 sec/ch

 

Interfaces

  • Relais Contacts NO/NC System OK+CH 1-4
  • Analogue Output: 4x 4-20mA (1 per Ch)
  • Analogue Input (OP Parameters): 8×4-20mA
  • Modbus RTU: RS-485
  • SB 2.0: PC communication

 

Display

  • Dimension: 4.3“
  • Resolution: 480x272pxl
  • Color Depth: 24bit
  • Touch: Resistive
  • Resolved Partial Discharge Pattern (Resolution: 256×256—16bit colour )
  • Bargraph: 4 (1 per Channel)
  • Trend: max. 1 Year (on Local Display)