Expert TMS-5141 Partial Discharge Monitor

Standalone, continuous partial discharge monitoring system with automatic data acquisition, storage, diagnostics, and trending.

Sensor Compatibility:

  • HFT Series Partial Discharge Sensor
  • HFTC Series Partial Discharge Sensor
  • PDC Series Partial Discharge Sensor

Description

The  Expert TMS-5141 is a four channel partial discharge trending system with a true color LCD to display all the necessary information for the commissioning and surveillance of  Medium Voltage and High Voltage Machines. The noise gating channel and variable LP Filter separates noise from actual partial discharge signals. The actual partial discharge levels for each individual channel (phase) are displayed on a  bar graph and real time partial discharge activities are displayed in oscilloscope view and through a colorised phase resolved pattern.

The touch functionality of the LCD display allows the user to set alarms and parameters, and to visualise the partial discharge signals without the use of an additional computer. Optionally a computer can be connected through the built in Ethernet Interface to store permanently measured results. The Modbus RTU interface allows an easy integration into the exisiting SCADA/DCS system. Individual 4-20mA and relay outputs per channel are available.

This makes the Expert TMS-5141 the ideal partial discharge monitoring system for permanent installation with permanent data recording.

Key Features

  • Online.
  • Continuous acquisition and monitoring.
  • Automatic data acquisition, storage, diagnostics, trending.
  • Built in local true color touch LCD.
  • Noise Elimination trough gating channel and variable frequency range
  • High Resolution PRPD Pattern
  • Intelligent analysis and diagnostics.
  • Integrated with SCADA and 3rd party monitoring systems.
  • 4 Analouge outputs, 8 inputs for operation parameter recording.
  • 100 Mbit Ethernet interface for permanent data storage.
  • IEC – 60270 compliant.

 

Technical Data

  • PD Input Channels (4 channel simultan + Gating): 4+1
  • Optional (pd channel extension to 16 channels)
  • Selectable LP Filter: 40KHz to 5MHz
  • Selectable HP Filter: 800kHz to 300MHz
  • Signal Gain (HW): 40dB
  • Acquisition Time Intervall: 1 to 600 sec/ch

 

Interfaces

  • Relais Contacts NO/NC System OK+CH 1-4
  • Analogue Output: 4x 4-20mA (1 per Ch)
  • Analogue Input (OP Parameters): 8×4-20mA
  • Modbus RTU: RS-485
  • Ethernet: 100Mbit/s

 

Display

  • Dimension: 4.3“
  • Resolution: 480x272pxl
  • Color Depth: 24bit
  • Touch: Resistive
  • Phase Resolved Partial Discharge Pattern (Resolution: 256×256—16bit colour )
  • Bargraph: 4 (1 per Channel)
  • Trend: max. 1 Year (on Local Display)
  • Event Logging